<law><site_title>Virginia Decoded</site_title><site_url>https://vacode.org</site_url><law_id>67636</law_id><section_number>40.1-51.10</section_number><catch_line>Right of access to premises; certification and recertification; inspection requirements</catch_line><edition url="https://vacode.org/2025/" slug="2025" current="TRUE" last_updated="">2025</edition><referred_to_by><reference>40.1-51.10:1</reference><reference>40.1-51.5</reference></referred_to_by><structure><unit label="title" level="1" order_by="1" identifier="40.1">Labor and Employment</unit><unit label="chapter" level="2" order_by="1" identifier="3.1">Boiler and Pressure Vessel Safety Act</unit><unit label="article" level="3" order_by="1" identifier="1">In General</unit></structure><text>
						<section id="A"><p><span class="prefix-number">A.</span> The <span class="dictionary">Commissioner</span>, his agents or special inspectors shall have free access, during reasonable hours to any premises in the Commonwealth where a <span class="dictionary">boiler</span> or pressure vessel is being constructed, operated or maintained, or is being installed to conduct a variance review, an <span class="dictionary">owner-user inspection agency</span> audit, an emergency repair review, an accident investigation, a violation follow-up, and a secondhand or used <span class="dictionary">boiler</span> review for the purpose of ascertaining whether such <span class="dictionary">boiler</span> or pressure vessel is being constructed, operated or maintained in accordance with this chapter. <a id="paragraph-245014" class="section-permalink" href="https://vacode.org/40.1-51.10/#A"><i class="fa fa-link"/></a></p></section>
						<section id="B"><p><span class="prefix-number">B.</span> On and after January 1, 1973, no <span class="dictionary">boiler</span> or pressure vessel used or proposed to be used within this Commonwealth, except <span class="dictionary">boilers</span> or pressure vessels exempted by this chapter, shall be installed, operated or maintained unless it has been inspected by the <span class="dictionary">Commissioner</span>, his agents or special inspectors as to construction, installation and condition and shall be certified. A fee as set under subsection A of &#xA7; <a class="law" title="Fees" href="/40.1-51.15/">40.1-51.15</a> shall be charged for each inspection certificate issued. In lieu of such fees both for certification and recertification, an authorized <span class="dictionary">owner-user inspection agency</span> shall be charged annual filing fees as set under subsection A of &#xA7; <a class="law" title="Fees" href="/40.1-51.15/">40.1-51.15</a>. <a id="paragraph-245015" class="section-permalink" href="https://vacode.org/40.1-51.10/#B"><i class="fa fa-link"/></a></p></section>
						<section id="C"><p><span class="prefix-number">C.</span> Recertification shall be required as follows: <a id="paragraph-245016" class="section-permalink" href="https://vacode.org/40.1-51.10/#C"><i class="fa fa-link"/></a></p></section>
						<section id="C1" class="indent-1"><p><span class="prefix-number">1.</span> <span class="dictionary">Power boilers</span> and <span class="dictionary">high pressure, high temperature water boilers</span> shall receive a <span class="dictionary">certificate inspection</span> annually and shall also be externally inspected annually while under pressure if possible; <a id="paragraph-245017" class="section-permalink" href="https://vacode.org/40.1-51.10/#C1"><i class="fa fa-link"/></a></p></section>
						<section id="C2" class="indent-1"><p><span class="prefix-number">2.</span> <span class="dictionary">Heating boilers</span> shall receive a <span class="dictionary">certificate inspection</span> biennially; <a id="paragraph-245018" class="section-permalink" href="https://vacode.org/40.1-51.10/#C2"><i class="fa fa-link"/></a></p></section>
						<section id="C3" class="indent-1"><p><span class="prefix-number">3.</span> Pressure vessels subject to internal corrosion shall receive a <span class="dictionary">certificate inspection</span> biennially; <a id="paragraph-245019" class="section-permalink" href="https://vacode.org/40.1-51.10/#C3"><i class="fa fa-link"/></a></p></section>
						<section id="C4" class="indent-1"><p><span class="prefix-number">4.</span> Pressure vessels not subject to internal corrosion shall receive a <span class="dictionary">certificate inspection</span> at intervals set by the <span class="dictionary">Board</span>, but internal inspection shall not be required of pressure vessels, the <span class="dictionary">content</span> of which are known to be noncorrosive to the <span class="dictionary">material</span> of which the shell, heads or fittings are constructed, either from the chemical composition of the <span class="dictionary">contents</span> or from <span class="dictionary">evidence</span> that the <span class="dictionary">contents</span> are adequately treated with a corrosion inhibitor, provided that such vessels are constructed in accordance with the rules and regulations of the <span class="dictionary">Board</span>; <a id="paragraph-245020" class="section-permalink" href="https://vacode.org/40.1-51.10/#C4"><i class="fa fa-link"/></a></p></section>
						<section id="C5" class="indent-1"><p><span class="prefix-number">5.</span> Nuclear vessels within the scope of this chapter shall be inspected and reported in such form and with such appropriate information as the <span class="dictionary">Board</span> shall designate; <a id="paragraph-245021" class="section-permalink" href="https://vacode.org/40.1-51.10/#C5"><i class="fa fa-link"/></a></p></section>
						<section id="C6" class="indent-1"><p><span class="prefix-number">6.</span> A grace period of two months beyond the periods specified in subdivisions 1, 2, 3 and 4 of this subsection may elapse between <span class="dictionary">certificate inspections</span>. The Chief Inspector may extend a certificate for up to three additional months beyond such grace period subject to a satisfactory external inspection of the <span class="dictionary">object</span> and receipt of a fee as set under subsection A of &#xA7; <a class="law" title="Fees" href="/40.1-51.15/">40.1-51.15</a> for each month of inspection beyond the grace period. <a id="paragraph-245022" class="section-permalink" href="https://vacode.org/40.1-51.10/#C6"><i class="fa fa-link"/></a></p></section>
						<section id="D"><p><span class="prefix-number">D.</span> Inspection requirements for operating equipment shall be in accordance with generally accepted practice and compatible with the actual service conditions and shall include but not be limited to the following criteria: <a id="paragraph-245023" class="section-permalink" href="https://vacode.org/40.1-51.10/#D"><i class="fa fa-link"/></a></p></section>
						<section id="D1" class="indent-1"><p><span class="prefix-number">1.</span> Previous experience, based on records of inspection, performance and maintenance; <a id="paragraph-245024" class="section-permalink" href="https://vacode.org/40.1-51.10/#D1"><i class="fa fa-link"/></a></p></section>
						<section id="D2" class="indent-1"><p><span class="prefix-number">2.</span> Location, with respect to personnel hazard; <a id="paragraph-245025" class="section-permalink" href="https://vacode.org/40.1-51.10/#D2"><i class="fa fa-link"/></a></p></section>
						<section id="D3" class="indent-1"><p><span class="prefix-number">3.</span> Qualifications and competency of inspection and operating personnel; <a id="paragraph-245026" class="section-permalink" href="https://vacode.org/40.1-51.10/#D3"><i class="fa fa-link"/></a></p></section>
						<section id="D4" class="indent-1"><p><span class="prefix-number">4.</span> Provision for related safe operation controls; and <a id="paragraph-245027" class="section-permalink" href="https://vacode.org/40.1-51.10/#D4"><i class="fa fa-link"/></a></p></section>
						<section id="D5" class="indent-1"><p><span class="prefix-number">5.</span> Interrelation with other operations outside of the scope of this chapter. <a id="paragraph-245028" class="section-permalink" href="https://vacode.org/40.1-51.10/#D5"><i class="fa fa-link"/></a></p></section>
						<section id="E"><p><span class="prefix-number">E.</span> Based upon documentation of such actual service conditions by the owner or user of the operating equipment, the <span class="dictionary">Board</span> may, in its discretion, permit variations in the inspection requirements as provided in this section. <a id="paragraph-245029" class="section-permalink" href="https://vacode.org/40.1-51.10/#E"><i class="fa fa-link"/></a></p></section>
						<section id="F"><p><span class="prefix-number">F.</span> If, at the discretion of the <span class="dictionary">Commissioner</span>, a hydrostatic test shall be deemed necessary, it shall be made by the owner or user of the <span class="dictionary">boiler</span> or pressure vessel. <a id="paragraph-245030" class="section-permalink" href="https://vacode.org/40.1-51.10/#F"><i class="fa fa-link"/></a></p></section>
						<section id="G"><p><span class="prefix-number">G.</span> All boilers, other than cast iron sectional boilers, and pressure vessels to be installed in this Commonwealth after the six-month period from the date upon which the rules and regulations of the <span class="dictionary">Board</span> shall become effective shall be inspected during construction as required by the applicable rules and regulations of the <span class="dictionary">Board</span>. <a id="paragraph-245031" class="section-permalink" href="https://vacode.org/40.1-51.10/#G"><i class="fa fa-link"/></a></p></section>
						<section id="H"><p><span class="prefix-number">H.</span> Ninety-one days after expiration of a certificate for any <span class="dictionary">boiler</span> or pressure vessel subject to this section, the <span class="dictionary">Commissioner</span> may assign an agent or special inspector to inspect such <span class="dictionary">boiler</span> or pressure vessel, and its owner or operator shall be assessed a fee for such inspection. The fee shall be established in accordance with subsection A of &#xA7; <a class="law" title="Fees" href="/40.1-51.15/">40.1-51.15</a>. <a id="paragraph-245032" class="section-permalink" href="https://vacode.org/40.1-51.10/#H"><i class="fa fa-link"/></a></p></section></text><history>1972, c. 237; 1974, c. 195; 1976, c. 288; 1986, c. 266; 1988, c. 289; 1992, c. 3; 1993, c. 544; 1995, c. 97; 1997, c. 212; 2005, c. 387.</history><metadata></metadata></law>